Favorite
Rated current from power, efficiency, and power factor, with the "≈2A per kW at 380V 3-phase" rule-of-thumb check.
Key points
Motor Rated Current: Rated current from power, efficiency, and power factor, with the "≈2A per kW at 380V 3-phase" rule-of-thumb check. Formula: I = P / (√3·U·η·cosφ) (three-phase). Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. Set the thermal relay to 1.05–1.1× rated current; size the VFD at 1.1–1.5×.
Inputs
I = P / (√3·U·η·cosφ) (three-phase)Calculation model (updates with parameters)
| Rated current I | 14.9 A | basis for contactor / thermal relay / wire |
| rule-of-thumb estimate | ≈ 15.0 A | Three-phase 380V: ≈2A per kW |
| input apparent power | 9.804 kVA | distribution capacity reference |
| startup current reference | 89 ~ 104 A | direct-on-line ≈5–7× rated |
Engineering notes
- Set the thermal relay to 1.05–1.1× rated current; size the VFD at 1.1–1.5×.
FAQ
- What is Motor Rated Current for?
- Rated current from power, efficiency, and power factor, with the "≈2A per kW at 380V 3-phase" rule-of-thumb check.
- What is the formula for Motor Rated Current?
- Core formula: I = P / (√3·U·η·cosφ) (three-phase). The tool returns results instantly using this formula and the selected parameters.
- What engineering notes should I keep in mind when using Motor Rated Current?
- Set the thermal relay to 1.05–1.1× rated current; size the VFD at 1.1–1.5×.
Embed this calculator on your site / blog / intranet
Copy the snippet below into any HTML-capable page — visitors get the same live calculator, styling included.
Related tools: Copper Busbar Ampacity Calculator (Heat-Balance Method)Busbar (Multi-Branch Collection) CalculatorAC Power / Power FactorThree-phase / Single-phase Power (Supply Standards)Transformer Ratio / TurnsTransformer Capacity ↔ Rated CurrentVoltage Drop / Wire Size CheckWire Cross-Section (Current)Reactance (XL / XC)Reactive Power CompensationEnergy / Electricity CostStar ↔ Delta Resistor ConversionMotor Sizing (Load Torque)AWG ↔ Metric Cross-SectionMotor Speed / Poles / SlipStar-Delta Starting Current / TorqueCircuit Breaker SelectionContactor / Thermal Overload Relay SelectionCT / Meter MultiplierTransformer Short-Circuit CurrentGround Resistance / ElectrodeElectric Heating Power / ConnectionDemand-Factor Load CalculationRCD (Residual Current Device) SelectionSPD (Surge Protective Device) SelectionConduit / Tray Fill SelectionCable Short-Circuit Thermal CheckCapacitor Current / Capacitance / Reactor RateVFD SelectionUPS Capacity / Battery BackupDiesel Generator SizingBusbar / Copper Bar SelectionMotor Protection Circuit Breaker (MPCB) Selection