Reactive Power Compensation
Favorite
Required kvar from current to target power factor — the cure for power-factor penalties.
Key points
Reactive Power Compensation: Required kvar from current to target power factor — the cure for power-factor penalties. Formula: Qc = P · (tanφ1 − tanφ2). Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. Compensating to ~0.95 is most economical; too high (>0.98) risks over-compensation oscillation — use automatic bank switching.
Inputs
Qc = P · (tanφ1 − tanφ2)Calculation model (updates with parameters)
| Required compensation Qc | 27.7 kvar | size the capacitor bank by this (round to standard kvar) |
| apparent power before compensation | 66.7 kVA | φ1 = 41° |
| apparent power after compensation | 52.6 kVA | release 14.0 kVA distribution capacity |
| current after compensation | reduced to 79% | line loss drops as I² |
Engineering notes
- Compensating to ~0.95 is most economical; too high (>0.98) risks over-compensation oscillation — use automatic bank switching.
FAQ
- What is Reactive Power Compensation for?
- Required kvar from current to target power factor — the cure for power-factor penalties.
- What is the formula for Reactive Power Compensation?
- Core formula: Qc = P · (tanφ1 − tanφ2). The tool returns results instantly using this formula and the selected parameters.
- What engineering notes should I keep in mind when using Reactive Power Compensation?
- Compensating to ~0.95 is most economical; too high (>0.98) risks over-compensation oscillation — use automatic bank switching.
Embed this calculator on your site / blog / intranet
Copy the snippet below into any HTML-capable page — visitors get the same live calculator, styling included.
Related tools: Copper Busbar Ampacity Calculator (Heat-Balance Method)Busbar (Multi-Branch Collection) CalculatorAC Power / Power FactorThree-phase / Single-phase Power (Supply Standards)Motor Rated CurrentTransformer Ratio / TurnsTransformer Capacity ↔ Rated CurrentVoltage Drop / Wire Size CheckWire Cross-Section (Current)Reactance (XL / XC)Energy / Electricity CostStar ↔ Delta Resistor ConversionMotor Sizing (Load Torque)AWG ↔ Metric Cross-SectionMotor Speed / Poles / SlipStar-Delta Starting Current / TorqueCircuit Breaker SelectionContactor / Thermal Overload Relay SelectionCT / Meter MultiplierTransformer Short-Circuit CurrentGround Resistance / ElectrodeElectric Heating Power / ConnectionDemand-Factor Load CalculationRCD (Residual Current Device) SelectionSPD (Surge Protective Device) SelectionConduit / Tray Fill SelectionCable Short-Circuit Thermal CheckCapacitor Current / Capacitance / Reactor RateVFD SelectionUPS Capacity / Battery BackupDiesel Generator SizingBusbar / Copper Bar SelectionMotor Protection Circuit Breaker (MPCB) Selection