Voltage Drop / Wire Size Check
Voltage drop percentage from conductor material and cross-section, and the minimum section for an allowed drop — essential for long runs.
Key points
Voltage Drop / Wire Size Check: Voltage drop percentage from conductor material and cross-section, and the minimum section for an allowed drop — essential for long runs. Formula: ΔU = 2·I·L·ρ/S (single-phase) | √3·I·L·ρ/S (three-phase). Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. Low motor terminal voltage causes torque collapse and heating; for long runs check voltage drop before current capacity.
Inputs
ΔU = 2·I·L·ρ/S (single-phase) | √3·I·L·ρ/S (three-phase)Calculation model (updates with parameters)
| Line voltage drop ΔU | 10.1 V | |
| Voltage drop percentage | 2.66% | requirement met |
| Minimum cross-section (drop ≤ 5.0%) | 3.19 mm² | Then take the larger of current-capacity and mechanical-strength requirements |
| line loss power (3 line) | 350 W | I²R heating loss |
Engineering notes
- Low motor terminal voltage causes torque collapse and heating; for long runs check voltage drop before current capacity.
FAQ
- What is Voltage Drop / Wire Size Check for?
- Voltage drop percentage from conductor material and cross-section, and the minimum section for an allowed drop — essential for long runs.
- What is the formula for Voltage Drop / Wire Size Check?
- Core formula: ΔU = 2·I·L·ρ/S (single-phase) | √3·I·L·ρ/S (three-phase). The tool returns results instantly using this formula and the selected parameters.
- What engineering notes should I keep in mind when using Voltage Drop / Wire Size Check?
- Low motor terminal voltage causes torque collapse and heating; for long runs check voltage drop before current capacity.