Voltage Drop / Wire Size Check

Favoriteused 1 times

Voltage drop percentage from conductor material and cross-section, and the minimum section for an allowed drop — essential for long runs.

Key points

Voltage Drop / Wire Size Check: Voltage drop percentage from conductor material and cross-section, and the minimum section for an allowed drop — essential for long runs. Formula: ΔU = 2·I·L·ρ/S (single-phase) | √3·I·L·ρ/S (three-phase). Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. Low motor terminal voltage causes torque collapse and heating; for long runs check voltage drop before current capacity.

Inputs

ΔU = 2·I·L·ρ/S (single-phase) | √3·I·L·ρ/S (three-phase)

Calculation model (updates with parameters)

supplyIloadline length L (ρ / S)ΔU = 10.1 V(2.7%)
Line voltage drop ΔU10.1 V
Voltage drop percentage2.66%
Minimum cross-section (drop ≤ 5.0%)3.19 mm²
line loss power (3 line)350 W

Engineering notes

  • Low motor terminal voltage causes torque collapse and heating; for long runs check voltage drop before current capacity.

FAQ

What is Voltage Drop / Wire Size Check for?
Voltage drop percentage from conductor material and cross-section, and the minimum section for an allowed drop — essential for long runs.
What is the formula for Voltage Drop / Wire Size Check?
Core formula: ΔU = 2·I·L·ρ/S (single-phase) | √3·I·L·ρ/S (three-phase). The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using Voltage Drop / Wire Size Check?
Low motor terminal voltage causes torque collapse and heating; for long runs check voltage drop before current capacity.