Active / reactive / apparent power from voltage, current and power factor, auto-switching single/three phase.
Key points
AC Power / Power Factor: Active / reactive / apparent power from voltage, current and power factor, auto-switching single/three phase. Formula: P = UI·cosφ | 3-phase S = √3·U·I | Q = S·sinφ. Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. In three-phase formulas U and I are line values (380V / line current).
Inputs
P = UI·cosφ | 3-phase S = √3·U·I | Q = S·sinφCalculation model (updates with parameters)
| Apparent power S | 6.582 kVA | √3·UI |
| Active power P | 5.595 kW | This is what the kWh meter measures |
| Reactive power Q | 3.467 kvar | uses capacity but does no work |
| Power factor | 0.85 | Below 0.9 may incur power-factor penalties |
⚠ Power factor <0.9: consider reactive compensation (see the power-factor compensation tool).
Engineering notes
- In three-phase formulas U and I are line values (380V / line current).
FAQ
- What is AC Power / Power Factor for?
- Active / reactive / apparent power from voltage, current and power factor, auto-switching single/three phase.
- What is the formula for AC Power / Power Factor?
- Core formula: P = UI·cosφ | 3-phase S = √3·U·I | Q = S·sinφ. The tool returns results instantly using this formula and the selected parameters.
- What engineering notes should I keep in mind when using AC Power / Power Factor?
- In three-phase formulas U and I are line values (380V / line current).
Embed this calculator on your site / blog / intranet
Copy the snippet below into any HTML-capable page — visitors get the same live calculator, styling included.
Related tools: Copper Busbar Ampacity Calculator (Heat-Balance Method)Busbar (Multi-Branch Collection) CalculatorThree-phase / Single-phase Power (Supply Standards)Motor Rated CurrentTransformer Ratio / TurnsTransformer Capacity ↔ Rated CurrentVoltage Drop / Wire Size CheckWire Cross-Section (Current)Reactance (XL / XC)Reactive Power CompensationEnergy / Electricity CostStar ↔ Delta Resistor ConversionMotor Sizing (Load Torque)AWG ↔ Metric Cross-SectionMotor Speed / Poles / SlipStar-Delta Starting Current / TorqueCircuit Breaker SelectionContactor / Thermal Overload Relay SelectionCT / Meter MultiplierTransformer Short-Circuit CurrentGround Resistance / ElectrodeElectric Heating Power / ConnectionDemand-Factor Load CalculationRCD (Residual Current Device) SelectionSPD (Surge Protective Device) SelectionConduit / Tray Fill SelectionCable Short-Circuit Thermal CheckCapacitor Current / Capacitance / Reactor RateVFD SelectionUPS Capacity / Battery BackupDiesel Generator SizingBusbar / Copper Bar SelectionMotor Protection Circuit Breaker (MPCB) Selection