Skip to main content
DD-CAT IDE logoDD-CAT IDE

4–20 mA Current Loop Converter

Favoriteused 2 times

Convert loop current to engineering units (temperature, pressure, level) and back, with percentage, sense-resistor drop and wire-break detection.

Key points

4–20 mA Current Loop Converter: Convert loop current to engineering units (temperature, pressure, level) and back, with percentage, sense-resistor drop and wire-break detection. Formula: Value = LRV + (I − 4mA)/16mA × (URV − LRV). Enter parameters on the DD-CAT IDE online tool page to get results instantly, with a calculation-model diagram that updates with the inputs. NAMUR NE43 defines < 3.6mA as wire break and > 21mA as saturation, which makes instrument diagnostics possible. A 250Ω resistor into a 5V ADC is the simplest front end; its accuracy sets the measurement error, so use 0.1% metal film.

Inputs

Value = LRV + (I − 4mA)/16mA × (URV − LRV)

Calculation model (updates with parameters)

4mA → 0 °C20mA → 100 °C12.00 mA · 50.0 %Transmitter2-wireRs250 ΩADC1~5 VI = 12.00 mA50.00 °CV_sense = 3 VADC 1~5 V
Engineering value50.000 °C
Percent of span50.00 %
Loop statusNormal (4–20 mA)
250Ω Sense resistorvoltage drop3.0000 V
Max total loop impedance (24V supply)1000 Ω

Engineering notes

  • NAMUR NE43 defines < 3.6mA as wire break and > 21mA as saturation, which makes instrument diagnostics possible.
  • A 250Ω resistor into a 5V ADC is the simplest front end; its accuracy sets the measurement error, so use 0.1% metal film.

FAQ

What is 4–20 mA Current Loop Converter for?
Convert loop current to engineering units (temperature, pressure, level) and back, with percentage, sense-resistor drop and wire-break detection.
What is the formula for 4–20 mA Current Loop Converter?
Core formula: Value = LRV + (I − 4mA)/16mA × (URV − LRV). The tool returns results instantly using this formula and the selected parameters.
What engineering notes should I keep in mind when using 4–20 mA Current Loop Converter?
NAMUR NE43 defines < 3.6mA as wire break and > 21mA as saturation, which makes instrument diagnostics possible. A 250Ω resistor into a 5V ADC is the simplest front end; its accuracy sets the measurement error, so use 0.1% metal film.
ShareWeiboXLinkedIn
Embed this calculator on your site / blog / intranet

Copy the snippet below into any HTML-capable page — visitors get the same live calculator, styling included.